IS-KTeS

Features

  • Tmax 260°C
  • Approx. 20 W/m
  • IP65
Request a quote Give us a call or send an email phonelink_ring +31 (0)183 - 20 10 88 forward_to_inbox sales@tc-e.nl

Application

Isopad IS-KTeS is a pre-terminated, PTFE insulated, heating cable suitable for use where no excessive mechanical loads are expected and moisture may be present. 

This flexible and easily installed cable provides inexpensive and versatile heating. Applications include heat tracing of pipes, small containers, tools, machines, extremely thin and short pipes, and machine parts with limited mounting space.

IS-KTeS product variants
SKU P/N Item Length ⁽¹⁾ Voltage Rating ⁽²⁾
ISS.A01.001 680108-000 IS-KTES/2.2M/230V/50W/KE1.5M 2.20 m 230 V 50 W
ISS.A01.002 970664-000 IS-KTES/4.4M/230V/100W/KE1.5M 4.40 m 230 V 100 W
ISS.A01.003 414978-000 IS-KTES/7.0M/230V/140W/KE1.5M 7.00 m 230 V 140 W
ISS.A01.004 869130-000 IS-KTES/11.0M/230V/250W/KE1.5M 11.00 m 230 V 250 W
ISS.A01.005 037962-000 IS-KTES/16.0M/230V/330W/KE1.5M 16.00 m 230 V 330 W
ISS.A01.006 927424-000 IS-KTES/22.0M/230V/500W/KE1.5M 22.00 m 230 V 500 W
ISS.A01.007 073216-000 IS-KTES/28.0M/230V/630W/KE1.5M 28.00 m 230 V 630 W
ISS.A01.008 206840-000 IS-KTES/40.0M/230V/920W/KE1.5M 40.00 m 230 V 920 W
ISS.A01.009 736072-000 IS-KTES/58.0M/230V/1300W/KE1.5M 58.00 m 230 V 1300 W
ISS.A01.010 380470-000 IS-KTES/80.0M/230V/1740W/KE1.5M 80.00 m 230 V 1740 W
ISS.A01.011 480964-000 IS-KTES/112.0M/230V/2360W/KE1.5M 112.00 m 230 V 2360 W
ISS.A01.012 335974-000 IS-KTES/156.0M/230V/3391W/KE1.5M 156.00 m 230 V 3391 W

Other lengths and power specifications, etc. available on request.

⁽¹⁾ Tolerances ± (2% + 100 mm)
⁽²⁾ Tolerances ±10%

Resources

Datasheet
English
German

Installation manual
English/German

Certifications/Approvals

CE

Specifications

General

Manufacturer
Chromalox
Brand
Isopad
Unit of measurement
Piece

Area specifications

Area classification
Nonhazardous, ordinary area
Ingress protection
IP65
Electrical protection class
Class I
Maximum withstand temperature (power off)
260°C
Maximum withstand temperature (power on)
Depends upon power

Standard manufacturing sizes

Outer diameter (OD)
2.5 to 3.5 mm

Heater construction

Type
Resistance heating cable
Material
Various alloys
Material of insulation
PTFE
Material of outer sheath
Copper-nickel braid

Lead connection

Connection length
Terminated at each end with a 1.5 m cold lead
Cross section
1.0 mm²
Maximum operating temperature
260°C
Insulation material
PTFE

Technical data

Frequency
50-60 Hz
Nominal operating voltage
230 Vac
Approximate power output per meter
20 W/m
Maximum operating temperature
260°C
Minimum bend radius
10 mm
Minimum spacing
5 mm