Application
Isopad IT-S45 is a preterminated, flexible heating tape consisting of a glassfiber insulated, flexible fabric weave with interior heating conductors. The protective overbraid of the coiled heating conductors meets the requirements of Protection Class I.
The temperature depends on the power and application. It is important to make sure that the heating tape does not exceed the maximum withstand temperature. This heating tape is typically used for heating up and compensating for heat losses on short pipes and small-sized structures. The heating tape is not moisture-protected and must only be used in dry areas.
SKU | P/N | Item | Length ⁽¹⁾ | Voltage | Rating ⁽²⁾ |
---|---|---|---|---|---|
ISS.A02.181 | 386552-000 | IT-S45/0.5M/230V/100W/KE1.0M | 0.50 m | 230 V | 100 W |
ISS.A02.182 | 542364-000 | IT-S45/1.0M/230V/250W/KE1.0M | 1.00 m | 230 V | 250 W |
ISS.A02.183 | 051330-000 | IT-S45/1.5M/230V/375W/KE1.0M | 1.50 m | 230 V | 375 W |
ISS.A02.184 | 111280-000 | IT-S45/2.0M/230V/500W/KE1.0M | 2.00 m | 230 V | 500 W |
ISS.A02.185 | 870574-000 | IT-S45/2.5M/230V/625W/KE1.0M | 2.50 m | 230 V | 625 W |
ISS.A02.186 | 873740-000 | IT-S45/3.0M/230V/750W/KE1.0M | 3.00 m | 230 V | 750 W |
ISS.A02.187 | 596276-000 | IT-S45/4.0M/230V/1000W/KE1.0M | 4.00 m | 230 V | 1000 W |
ISS.A02.188 | 932450-000 | IT-S45/5.0M/230V/1250W/KE1.0M | 5.00 m | 230 V | 1250 W |
Other lengths and power specifications, etc. available upon request.
⁽¹⁾ Tolerances
<2000 mm ± (1% + 50 mm)
>2000 mm ± (2% + 100 mm)
⁽²⁾ Tolerances ±10%
Certifications/Approvals
CE
Specifications
General
- Manufacturer
- Chromalox
- Brand
- Isopad
- Unit of measurement
- Piece
Area specifications
- Area classification
- Nonhazardous, ordinary area
- Ingress protection
- IP20
- Electrical protection class
- Class I
- Maximum withstand temperature (power off)
- 450°C
- Storage temperature
- –40 to +50°C
- Minimum installation temperature
- –40°C
Standard manufacturing sizes
- Width
- 30 mm ±10%
- Thickness
- 5 mm ±10%
Heater construction
- Type
- Resistance heating cable
- Material
- Nickel-chrome-alloy
- Material of insulation
- Glass-silk
- Material of outer sheath
- Copper-nickel braid
- Carrier
- Glass-silk woven fabric
Lead connection
- Connection length
- 1.0 m
- Cross section
- 2 x 1.0 mm²
- Maximum operating temperature
- 200°C
- Insulation material
- PTFE
Technical data
- Frequency
- 50-60 Hz
- Nominal operating voltage
- 230 Vac
- Approximate power output per meter
- 250 W/m
- Maximum operating temperature
- 450°C
- Minimum bend radius
- 15 mm
- Minimum spacing
- 5 mm