Application
Isopad IMI-KMV is a preterminated, mineral insulated heating cable consisting of a nickel-chrome 8020 heating element and a stainless-steel 1.451 / 321 metal sheath.
The connection joints between the heating cable and cold ends are welded using heavy duty lasers. At heating conductor temperatures up to 800°C, this cable is mainly used for heating elements with special forms, pipe trace heating in the chemical industry, form/platen heating, container heating, and special heaters for aqueous solutions.
The heating cable is watertight and can be used under both high pressure and vacuum conditions. IMI-KMV is ideally suited for transferring large thermal volumes as high per-meter load is possible under appropriate conditions.
SKU | P/N | Item | Length ⁽¹⁾ | Voltage | Rating ⁽²⁾ |
---|---|---|---|---|---|
ISS.A05.001 | 1235-04532007 | IMI-KMV/3.1M/110V/620W/KE0.5M | 3.10 m | 110 V | 620 W |
ISS.A05.002 | 1235-04532010 | IMI-KMV/5.0M/230V/1058W/KE0.5M | 5.00 m | 230 V | 1058 W |
ISS.A05.003 | 1235-04532011 | IMI-KMV/6.0M/230V/1400W/KE0.5M | 6.00 m | 230 V | 1400 W |
ISS.A05.004 | 1235-04532012 | IMI-KMV/7.5M/230V/1763W/KE0.5M | 7.50 m | 230 V | 1763 W |
ISS.A05.005 | 1235-04532013 | IMI-KMV/10.0M/230V/2116W/KE0.5M | 10.00 m | 230 V | 2116 W |
ISS.A05.006 | 1235-04532014 | IMI-KMV/12.5M/230V/2645W/KE0.5M | 12.50 m | 230 V | 2645 W |
ISS.A05.007 | 1235-04532015 | IMI-KMV/15.5M/230V/3413W/KE0.5M | 15.50 m | 230 V | 3413 W |
ISS.A05.008 | 1235-04532016 | IMI-KMV/19.5M/230V/4306W/KE0.5M | 19.50 m | 230 V | 4306 W |
ISS.A05.009 | 1235-04532018 | IMI-KMV/31.0M/230V/6823W/KE0.5M | 31.00 m | 230 V | 6826 W |
ISS.A05.010 | 1235-04532019 | IMI-KMV/41.0M/230V/8064W/KE0.5M | 41.00 m | 230 V | 8132 W |
Other lengths and power specifications, etc. available upon request.
⁽¹⁾ Tolerances
<2000 mm ± 1% and ± 0,05 m (cold lead ± 10%)
>2000 mm ± 2% and ± 0,1 m (cold lead ± 10%)
⁽²⁾ Tolerances ±10%
Certifications/Approvals
CE
Specifications
General
- Manufacturer
- Chromalox
- Brand
- Isopad
- Unit of measurement
- Piece
Area specifications
- Area classification
- Nonhazardous, ordinary area
- Ingress protection
- IP68
- Electrical protection class
- Class I
- Maximum withstand temperature (power off)
- 700°C ±10% (800°C on request)
- Minimum installation temperature
- –60°C
Heater construction
- Type
- Resistance heating cable
- Material
- Nickel-chrome-alloy
- Material of insulation
- Magnesium oxide (MgO)
- Material of outer sheath
- Stainless steel
Lead connection
- Glands
- Standard M20
- Connection length
- 0.5 m ±10% cold lead at each end
Technical data
- Maximum operating voltage
- 300 / 500 Vac
- Maximum operating temperature
- 700°C (800°C on request)
- Minimum bend radius
- 6 x OD
- Minimum spacing
- 25 mm